Site Acceptance Checklist for Steel Sections
A practical checklist for receiving gypsum board steel sections on site: paperwo...
Five values to pull from the spec, drawings and BOQ before ordering any section: base thickness, coating, depth, reference standard and deflection limit, with two worked examples and a pre-PO checklist.
Reading project specs to pick the right section means pulling five values out of the contract documents before writing a purchase order: base metal thickness in millimetres (not the coated total), zinc coating mass in grams per square metre, section depth in millimetres, the named reference standard such as ASTM C645 or EN 14195, and the deflection limit such as L/240. They are split between Division 09 of the specification, the partition and ceiling schedules on the drawings, and the BOQ item text. When all five match the section data sheet, you have the right section. When the documents disagree, the contract's order of precedence decides, and you raise an RFI before buying.
Read Part 2 for what to buy, Part 3 for how much, and Part 1 for what paperwork must travel with the order.
Five translations come up on almost every job:
The partition schedule shows type P2: 100 mm overall, one 12.5 mm board each side, 3.6 m floor to soffit. The spec reads: framing to ASTM C645, 0.5 mm base metal minimum, G60, studs at 400 mm centres, L/240 at 240 Pa.
Turned into an order:
Before confirming, check a height table. A 75 mm stud at 0.5 mm and 400 mm centres typically reaches 3.5 to 4.2 m at L/240 in common manufacturer tables, but the band depends on the exact profile. Get the table for the section you are buying and file it with the submittal.
The RCP shows a ceiling at 2.8 m under a slab at 3.3 m, a 500 mm drop, with a perimeter cove. The spec reads: main channels and hangers at 1200 mm maximum, furring at 400 mm centres, 12.5 mm board.
The load behind these numbers: a 12.5 mm board weighs about 10 kg/m2 and the metal grid 2 to 3 kg/m2, so the suspension is usually designed for at least 15 kg/m2 with margin for services. Changing hanger spacing needs the consultant's approval, not the supplier's.
Treat the spec as a five-value table you build yourself, not a document read once and filed. Keep one page per partition or ceiling type with base thickness, coating, depth, reference and performance limits, signed by the consultant before the first order. When the truck arrives, that page is your receiving checklist. When the parties disagree a year later, it is the evidence.
Use the conversion in ASTM C645 or ASTM A653 rather than a generic web table, because galvanized sheet gauge differs from black sheet gauge. The two most common values are 25 gauge at 0.455 mm and 20 gauge at 0.836 mm base metal. Write the millimetre value on the PO and state that it is base metal before coating.
Base metal thickness is the steel alone before galvanizing. Total thickness includes the zinc on both faces, about 0.04 mm more at Z275. Specs quote base metal because that is what carries load, while a site micrometer reads total. If the order does not say which you mean, you can receive a section about 0.04 mm thinner than intended that still matches the order literally.
Usually yes, but not automatically. First check the overall partition thickness in the schedule, since an extra 5 mm can clash with a door frame or a junction detail. Then submit the section data sheet and its height table to the consultant as a substitution request and get written approval before buying. If the partition is part of a fire-rated system, the substitution also has to be covered by the test report.
Yes. The consultant will ask for it in the submittal regardless of height, and the table is the only proof that the section, thickness and spacing you chose meet the deflection limit. A 4.8 cm stud in a light thickness can be close to its limit at that height in some tables, so the check is not a formality.
Do not decide on your own. Go to the order of precedence clause in the contract conditions. In most contracts the specification outranks the BOQ on material description. Raise a formal RFI quoting both clauses and asking for a ruling, and keep the answer with the PO, because the thickness difference affects both price and allowable height.